# CVE ID CWE ID # of Exploits Vulnerability Type(s) Publish Date Update Date Score Gained Access Level Access Complexity Authentication Conf. Integ. Avail.
1 CVE-2019-6545 99 2019-02-12 2019-10-09
10.0
None Remote Low Not required Complete Complete Complete
AVEVA Software, LLC InduSoft Web Studio prior to Version 8.1 SP3 and InTouch Edge HMI (formerly InTouch Machine Edition) prior to Version 2017 Update. An unauthenticated remote user could use a specially crafted database connection configuration file to execute an arbitrary process on the server machine.
2 CVE-2019-6543 306 Exec Code 2019-02-12 2019-10-09
10.0
None Remote Low Not required Complete Complete Complete
AVEVA Software, LLC InduSoft Web Studio prior to Version 8.1 SP3 and InTouch Edge HMI (formerly InTouch Machine Edition) prior to Version 2017 Update. Code is executed under the program runtime privileges, which could lead to the compromise of the machine.
3 CVE-2019-6525 255 2019-04-11 2019-04-12
4.0
None Remote Low Single system Partial None None
AVEVA Wonderware System Platform 2017 Update 2 and prior uses an ArchestrA network user account for authentication of system processes and inter-node communications. A user with low privileges could make use of an API to obtain the credentials for this account.
4 CVE-2018-17916 119 Exec Code Overflow 2018-11-02 2019-10-09
10.0
None Remote Low Not required Complete Complete Complete
InduSoft Web Studio versions prior to 8.1 SP2, and InTouch Edge HMI (formerly InTouch Machine Edition) versions prior to 2017 SP2. A remote attacker could send a carefully crafted packet to exploit a stack-based buffer overflow vulnerability during tag, alarm, or event related actions such as read and write, with potential for code to be executed. If InduSoft Web Studio remote communication security was not enabled, or a password was left blank, a remote user could send a carefully crafted packet to invoke an arbitrary process, with potential for code to be executed. The code would be executed under the privileges of the InduSoft Web Studio or InTouch Edge HMI runtime and could lead to a compromise of the InduSoft Web Studio or InTouch Edge HMI server machine.
5 CVE-2018-17914 Exec Code 2018-11-02 2019-10-09
10.0
None Remote Low Not required Complete Complete Complete
InduSoft Web Studio versions prior to 8.1 SP2, and InTouch Edge HMI (formerly InTouch Machine Edition) versions prior to 2017 SP2. This vulnerability could allow an unauthenticated user to remotely execute code with the same privileges as that of the InduSoft Web Studio or InTouch Edge HMI (formerly InTouch Machine Edition) runtime.
6 CVE-2018-10628 119 Exec Code Overflow 2018-07-24 2019-10-09
7.5
None Remote Low Not required Partial Partial Partial
AVEVA InTouch 2014 R2 SP1 and prior, InTouch 2017, InTouch 2017 Update 1, and InTouch 2017 Update 2 allow an unauthenticated user to send a specially crafted packet that could overflow the buffer on a locale not using a dot floating point separator. Exploitation could allow remote code execution under the privileges of the InTouch View process.
7 CVE-2018-10620 119 Exec Code Overflow 2018-07-19 2019-10-09
7.5
None Remote Low Not required Partial Partial Partial
AVEVA InduSoft Web Studio v8.1 and v8.1SP1, and InTouch Machine Edition v2017 8.1 and v2017 8.1 SP1 a remote user could send a carefully crafted packet to exploit a stack-based buffer overflow vulnerability during tag, alarm, or event related actions such as read and write, with potential for code to be executed.
8 CVE-2017-9962 119 Overflow 2017-09-25 2018-12-31
5.0
None Remote Low Not required None None Partial
Schneider Electric's ClearSCADA versions released prior to August 2017 are susceptible to a memory allocation vulnerability, whereby malformed requests can be sent to ClearSCADA client applications to cause unexpected behavior. Client applications affected include ViewX and the Server Icon.
9 CVE-2017-6021 20 2018-05-14 2019-10-09
5.0
None Remote Low Not required None None Partial
In Schneider Electric ClearSCADA 2014 R1 (build 75.5210) and prior, 2014 R1.1 (build 75.5387) and prior, 2015 R1 (build 76.5648) and prior, and 2015 R2 (build 77.5882) and prior, an attacker with network access to the ClearSCADA server can send specially crafted sequences of commands and data packets to the ClearSCADA server that can cause the ClearSCADA server process and ClearSCADA communications driver processes to terminate. A CVSS v3 base score of 7.5 has been assigned; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).
10 CVE-2014-5413 310 2014-09-18 2018-12-31
5.0
None Remote Low Not required None Partial None
Schneider Electric StruxureWare SCADA Expert ClearSCADA 2010 R3 through 2014 R1 uses the MD5 algorithm for an X.509 certificate, which makes it easier for remote attackers to spoof servers via a cryptographic attack against this algorithm.
11 CVE-2014-5412 264 2014-09-18 2018-12-31
5.0
None Remote Low Not required Partial None None
Schneider Electric StruxureWare SCADA Expert ClearSCADA 2010 R3 through 2014 R1 allows remote attackers to read database records by leveraging access to the guest account.
12 CVE-2014-5411 79 XSS 2014-09-18 2018-12-31
3.5
None Remote Medium Single system None Partial None
Multiple cross-site scripting (XSS) vulnerabilities in Schneider Electric StruxureWare SCADA Expert ClearSCADA 2010 R3 through 2014 R1 allow remote authenticated users to inject arbitrary web script or HTML via unspecified vectors.
13 CVE-2014-0779 119 DoS Overflow 2014-03-14 2018-12-31
6.8
None Remote Medium Not required Partial Partial Partial
The PLC driver in ServerMain.exe in the Kepware KepServerEX 4 component in Schneider Electric StruxureWare SCADA Expert ClearSCADA 2010 R2 build 71.4165, 2010 R2.1 build 71.4325, 2010 R3 build 72.4560, 2010 R3.1 build 72.4644, 2013 R1 build 73.4729, 2013 R1.1 build 73.4832, 2013 R1.1a build 73.4903, 2013 R1.2 build 73.4955, and 2013 R2 build 74.5094 allows remote attackers to cause a denial of service (application crash) via a crafted OPF file (aka project file).
14 CVE-2013-6142 399 DoS 2014-01-15 2018-12-31
4.3
None Remote Medium Not required None None Partial
DNP3Driver.exe in the DNP3 driver in Schneider Electric ClearSCADA 2010 R2 through 2010 R3.1 and SCADA Expert ClearSCADA 2013 R1 through 2013 R1.2 allows remote attackers to cause a denial of service (resource consumption) via IP packets containing errors that trigger event-journal messages.
15 CVE-2011-3144 79 XSS 2011-08-16 2018-12-31
4.3
None Remote Medium Not required None Partial None
Cross-site scripting (XSS) vulnerability in Control Microsystems ClearSCADA 2005, 2007, and 2009 before R2.3 and R1.4, as used in SCX before 67 R4.5 and 68 R3.9, allows remote attackers to inject arbitrary web script or HTML via unspecified vectors.
16 CVE-2011-3143 399 DoS Exec Code Mem. Corr. 2011-08-16 2018-12-31
10.0
None Remote Low Not required Complete Complete Complete
Use-after-free vulnerability in Control Microsystems ClearSCADA 2005, 2007, and 2009 before R2.3 and R1.4, as used in SCX before 67 R4.5 and 68 R3.9, allows remote attackers to cause a denial of service (crash) and possibly execute arbitrary code via unspecified long strings that trigger heap memory corruption.
Total number of vulnerabilities : 16   Page : 1 (This Page)
CVE is a registred trademark of the MITRE Corporation and the authoritative source of CVE content is MITRE's CVE web site. CWE is a registred trademark of the MITRE Corporation and the authoritative source of CWE content is MITRE's CWE web site. OVAL is a registered trademark of The MITRE Corporation and the authoritative source of OVAL content is MITRE's OVAL web site.
Use of this information constitutes acceptance for use in an AS IS condition. There are NO warranties, implied or otherwise, with regard to this information or its use. Any use of this information is at the user's risk. It is the responsibility of user to evaluate the accuracy, completeness or usefulness of any information, opinion, advice or other content. EACH USER WILL BE SOLELY RESPONSIBLE FOR ANY consequences of his or her direct or indirect use of this web site. ALL WARRANTIES OF ANY KIND ARE EXPRESSLY DISCLAIMED. This site will NOT BE LIABLE FOR ANY DIRECT, INDIRECT or any other kind of loss.