On Triangle MicroWorks' SCADA Data Gateway version <= v5.01.03, an unauthenticated attacker can send a specially crafted broadcast message including format string characters to the SCADA Data Gateway to perform unrestricted memory reads.An unauthenticated user can use this format string vulnerability to repeatedly crash the GTWWebMonitor.exe process to DoS the Web Monitor. Furthermore, an authenticated user can leverage this vulnerability to leak memory from the GTWWebMonitor.exe process. This could be leveraged in an exploit chain to gain code execution.
Max CVSS
9.8
EPSS Score
0.14%
Published
2023-06-07
Updated
2023-06-16
The Triangle Microworks IEC 61850 Library (Any client or server using the C language library with a version number of 11.2.0 or earlier and any client or server using the C++, C#, or Java language library with a version number of 5.0.1 or earlier) and 60870-6 (ICCP/TASE.2) Library (Any client or server using a C++ language library with a version number of 4.4.3 or earlier) are vulnerable to access given to a small number of uninitialized pointers within their code. This could allow an attacker to target any client or server using the affected libraries to cause a denial-of-service condition.
Max CVSS
7.5
EPSS Score
0.08%
Published
2022-10-11
Updated
2022-10-21
Triangle MicroWorks SCADA Data Gateway 3.02.0697 through 4.0.122, 2.41.0213 through 4.0.122 allows remote attackers cause a denial-of-service condition due to a lack of proper validation of the length of user-supplied data, prior to copying it to a fixed-length stack-based buffer. Authentication is not required to exploit this vulnerability.
Max CVSS
7.5
EPSS Score
0.31%
Published
2020-04-15
Updated
2020-04-22
Triangle MicroWorks SCADA Data Gateway 3.02.0697 through 4.0.122, 2.41.0213 through 4.0.122 allows remote attackers to disclose sensitive information due to the lack of proper validation of user-supplied data, which can result in a read past the end of an allocated structure. Authentication is not required to exploit this vulnerability. Only applicable to installations using DNP3 Data Sets.
Max CVSS
7.5
EPSS Score
0.72%
Published
2020-04-15
Updated
2020-04-22
Triangle MicroWorks SCADA Data Gateway 3.02.0697 through 4.0.122, 2.41.0213 through 4.0.122 allows remote attackers to execute arbitrary code due to the lack of proper validation of user-supplied data, which can result in a type confusion condition. Authentication is not required to exploit this vulnerability. Only applicable to installations using DNP3 Data Sets.
Max CVSS
9.8
EPSS Score
0.49%
Published
2020-04-15
Updated
2020-04-22
Triangle MicroWorks DNP3 Outstation LibrariesDNP3 Outstation .NET Protocol components and DNP3 Outstation ANSI C source code libraries are affected:3.16.00 through 3.25.01. A specially crafted message may cause a stack-based buffer overflow. Authentication is not required to exploit this vulnerability.
Max CVSS
9.8
EPSS Score
0.33%
Published
2020-04-15
Updated
2020-04-22
Triangle MicroWorks SCADA Data Gateway 2.50.0309 through 3.00.0616, DNP3 .NET Protocol components 3.06.0.171 through 3.15.0.369, and DNP3 C libraries 3.06.0000 through 3.15.0000 allow remote attackers to cause a denial of service (infinite loop) via a crafted DNP3 TCP packet.
Max CVSS
7.8
EPSS Score
0.19%
Published
2013-09-09
Updated
2013-09-25
7 vulnerabilities found