Vulnerability Details : CVE-2022-34819
A vulnerability has been identified in SIMATIC CP 1242-7 V2 (All versions < V3.3.46), SIMATIC CP 1243-1 (All versions < V3.3.46), SIMATIC CP 1243-7 LTE EU (All versions < V3.3.46), SIMATIC CP 1243-7 LTE US (All versions < V3.3.46), SIMATIC CP 1243-8 IRC (All versions < V3.3.46), SIMATIC CP 1542SP-1 IRC (All versions >= V2.0 < V2.2.28), SIMATIC CP 1543-1 (All versions < V3.0.22), SIMATIC CP 1543SP-1 (All versions >= V2.0 < V2.2.28), SIPLUS ET 200SP CP 1542SP-1 IRC TX RAIL (All versions >= V2.0 < V2.2.28), SIPLUS ET 200SP CP 1543SP-1 ISEC (All versions >= V2.0 < V2.2.28), SIPLUS ET 200SP CP 1543SP-1 ISEC TX RAIL (All versions >= V2.0 < V2.2.28), SIPLUS NET CP 1242-7 V2 (All versions < V3.3.46), SIPLUS NET CP 1543-1 (All versions < V3.0.22), SIPLUS S7-1200 CP 1243-1 (All versions < V3.3.46), SIPLUS S7-1200 CP 1243-1 RAIL (All versions < V3.3.46). The application lacks proper validation of user-supplied data when parsing specific messages. This could result in a heap-based buffer overflow. An attacker could leverage this vulnerability to execute code in the context of device.
Vulnerability category: OverflowMemory CorruptionExecute code
Products affected by CVE-2022-34819
- cpe:2.3:o:siemens:simatic_cp_1543-1_firmware:*:*:*:*:*:*:*:*
- cpe:2.3:o:siemens:simatic_cp_1243-1_firmware:*:*:*:*:*:*:*:*
- cpe:2.3:o:siemens:simatic_cp_1542sp-1_irc_firmware:*:*:*:*:*:*:*:*
- cpe:2.3:o:siemens:simatic_cp_1543sp-1_firmware:*:*:*:*:*:*:*:*
- cpe:2.3:o:siemens:siplus_et_200sp_cp_1542sp-1_irc_tx_rail_firmware:*:*:*:*:*:*:*:*
- cpe:2.3:o:siemens:siplus_et_200sp_cp_1543sp-1_isec_firmware:*:*:*:*:*:*:*:*
- cpe:2.3:o:siemens:siplus_s7-1200_cp_1243-1_rail_firmware:*:*:*:*:*:*:*:*
- cpe:2.3:o:siemens:siplus_s7-1200_cp_1243-1_firmware:*:*:*:*:*:*:*:*
- cpe:2.3:o:siemens:siplus_net_cp_1543-1_firmware:*:*:*:*:*:*:*:*
- cpe:2.3:o:siemens:siplus_et_200sp_cp_1543sp-1_isec_tx_rail_firmware:*:*:*:*:*:*:*:*
- cpe:2.3:o:siemens:simatic_cp_1242-7_v2_firmware:*:*:*:*:*:*:*:*
- cpe:2.3:o:siemens:simatic_cp_1243-7_lte_eu_firmware:*:*:*:*:*:*:*:*
- cpe:2.3:o:siemens:simatic_cp_1243-7_lte_us_firmware:*:*:*:*:*:*:*:*
- cpe:2.3:o:siemens:simatic_cp_1243-8_irc_firmware:*:*:*:*:*:*:*:*
- cpe:2.3:o:siemens:siplus_net_cp_1242-7_v2_firmware:*:*:*:*:*:*:*:*
Exploit prediction scoring system (EPSS) score for CVE-2022-34819
0.14%
Probability of exploitation activity in the next 30 days
EPSS Score History
~ 49 %
Percentile, the proportion of vulnerabilities that are scored at or less
CVSS scores for CVE-2022-34819
Base Score | Base Severity | CVSS Vector | Exploitability Score | Impact Score | Score Source | First Seen |
---|---|---|---|---|---|---|
9.3
|
HIGH | AV:N/AC:M/Au:N/C:C/I:C/A:C |
8.6
|
10.0
|
NIST | |
10.0
|
CRITICAL | CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:C/C:H/I:H/A:H |
3.9
|
6.0
|
NIST | |
10.0
|
CRITICAL | CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:C/C:H/I:H/A:H |
3.9
|
6.0
|
Siemens AG |
CWE ids for CVE-2022-34819
-
A heap overflow condition is a buffer overflow, where the buffer that can be overwritten is allocated in the heap portion of memory, generally meaning that the buffer was allocated using a routine such as malloc().Assigned by: productcert@siemens.com (Primary)
-
The product writes data past the end, or before the beginning, of the intended buffer.Assigned by: nvd@nist.gov (Secondary)
References for CVE-2022-34819
-
https://cert-portal.siemens.com/productcert/pdf/ssa-517377.pdf
Patch;Vendor Advisory