A CWE-22: Improper Limitation of a Pathname to a Restricted Directory ('Path Traversal') vulnerability exists that could cause unauthorized firmware image loading when unsigned images are added to the firmware image path. Affected Products: X80 advanced RTU Communication Module (BMENOR2200H) (V2.01 and later), OPC UA Modicon Communication Module (BMENUA0100) (V1.10 and prior)
Vulnerability category: Directory traversal
Products affected by CVE-2022-34762
- cpe:2.3:o:schneider-electric:opc_ua_module_for_m580_firmware:*:*:*:*:*:*:*:*
- cpe:2.3:o:schneider-electric:x80_advanced_rtu_module_firmware:*:*:*:*:*:*:*:*
Exploit prediction scoring system (EPSS) score for CVE-2022-34762
0.09%
Probability of exploitation activity in the next 30 days
EPSS Score History
~ 36 %
Percentile, the proportion of vulnerabilities that are scored at or less
CVSS scores for CVE-2022-34762
Base Score | Base Severity | CVSS Vector | Exploitability Score | Impact Score | Score Source | First Seen |
---|---|---|---|---|---|---|
5.9
|
MEDIUM | CVSS:3.1/AV:N/AC:H/PR:H/UI:N/S:U/C:N/I:H/A:H |
0.7
|
5.2
|
Schneider Electric SE | |
7.5
|
HIGH | CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:H/A:N |
3.9
|
3.6
|
NIST |
CWE ids for CVE-2022-34762
-
The product uses external input to construct a pathname that is intended to identify a file or directory that is located underneath a restricted parent directory, but the product does not properly neutralize special elements within the pathname that can cause the pathname to resolve to a location that is outside of the restricted directory.Assigned by: cybersecurity@se.com (Primary)