Vulnerability Details : CVE-2022-30316
Honeywell Experion PKS Safety Manager 5.02 has Insufficient Verification of Data Authenticity. According to FSCT-2022-0054, there is a Honeywell Experion PKS Safety Manager unauthenticated firmware update issue. The affected components are characterized as: Firmware update functionality. The potential impact is: Firmware manipulation. The Honeywell Experion PKS Safety Manager utilizes the DCOM-232/485 communication FTA serial interface and Enea POLO bootloader for firmware management purposes. An engineering workstation running the Safety Builder software communicates via serial or serial-over-ethernet link with the DCOM-232/485 interface. Firmware images were found to have no authentication (in the form of firmware signing) and only relied on insecure checksums for regular integrity checks. Firmware images are unsigned. An attacker with access to the serial interface (either through physical access, a compromised EWS or an exposed serial-to-ethernet gateway) can utilize hardcoded credentials (see FSCT-2022-0052) for the POLO bootloader to control the boot process and push malicious firmware images to the controller allowing for firmware manipulation, remote code execution and denial of service impacts. A mitigating factor is that in order for a firmware update to be initiated, the Safety Manager has to be rebooted which is typically done by means of physical controls on the Safety Manager itself. As such, an attacker would have to either lay dormant until a legitimate reboot occurs or possibly attempt to force a reboot through a secondary vulnerability.
Vulnerability category: Execute codeDenial of service
Products affected by CVE-2022-30316
- cpe:2.3:o:honeywell:safety_manager_firmware:-:*:*:*:*:*:*:*
Exploit prediction scoring system (EPSS) score for CVE-2022-30316
0.18%
Probability of exploitation activity in the next 30 days
EPSS Score History
~ 55 %
Percentile, the proportion of vulnerabilities that are scored at or less
CVSS scores for CVE-2022-30316
Base Score | Base Severity | CVSS Vector | Exploitability Score | Impact Score | Score Source | First Seen |
---|---|---|---|---|---|---|
6.8
|
MEDIUM | CVSS:3.1/AV:P/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H |
0.9
|
5.9
|
NIST |
CWE ids for CVE-2022-30316
-
The product does not validate or incorrectly validates the integrity check values or "checksums" of a message. This may prevent it from detecting if the data has been modified or corrupted in transmission.Assigned by: nvd@nist.gov (Primary)
References for CVE-2022-30316
-
https://www.forescout.com/blog/
Blog - ForescoutThird Party Advisory
-
https://www.cisa.gov/uscert/ics/advisories/icsa-22-207-02
Honeywell Safety Manager | CISAMitigation;Third Party Advisory;US Government Resource