Vulnerability Details : CVE-2022-30312
The Trend Controls IC protocol through 2022-05-06 allows Cleartext Transmission of Sensitive Information. According to FSCT-2022-0050, there is a Trend Controls Inter-Controller (IC) protocol cleartext transmission of credentials issue. The affected components are characterized as: Inter-Controller (IC) protocol (57612/UDP). The potential impact is: Compromise of credentials. Several Trend Controls building automation controllers utilize the Inter-Controller (IC) protocol in for information exchange and automation purposes. This protocol offers authentication in the form of a 4-digit PIN in order to protect access to sensitive operations like strategy uploads and downloads as well as optional 0-30 character username and password protection for web page access protection. Both the PIN and usernames and passwords are transmitted in cleartext, allowing an attacker with passive interception capabilities to obtain these credentials. Credentials are transmitted in cleartext. An attacker who obtains Trend IC credentials can carry out sensitive engineering actions such as manipulating controller strategy or configuration settings. If the credentials in question are (re)used for other applications, their compromise could potentially facilitate lateral movement.
Products affected by CVE-2022-30312
- cpe:2.3:o:honeywell:trend_iq412_firmware:*:*:*:*:*:*:*:*
- cpe:2.3:o:honeywell:trend_iq411_firmware:*:*:*:*:*:*:*:*
- cpe:2.3:o:honeywell:trend_iq422_firmware:*:*:*:*:*:*:*:*
- cpe:2.3:o:honeywell:trend_iq4nc_firmware:*:*:*:*:*:*:*:*
- cpe:2.3:o:honeywell:trend_iq4e_firmware:*:*:*:*:*:*:*:*
Exploit prediction scoring system (EPSS) score for CVE-2022-30312
0.02%
Probability of exploitation activity in the next 30 days
EPSS Score History
~ 4 %
Percentile, the proportion of vulnerabilities that are scored at or less
CVSS scores for CVE-2022-30312
Base Score | Base Severity | CVSS Vector | Exploitability Score | Impact Score | Score Source | First Seen |
---|---|---|---|---|---|---|
6.5
|
MEDIUM | CVSS:3.1/AV:A/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N |
2.8
|
3.6
|
134c704f-9b21-4f2e-91b3-4a467353bcc0 | 2025-06-17 |
6.5
|
MEDIUM | CVSS:3.1/AV:A/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N |
2.8
|
3.6
|
NIST |
CWE ids for CVE-2022-30312
-
The product transmits sensitive or security-critical data in cleartext in a communication channel that can be sniffed by unauthorized actors.Assigned by:
- 134c704f-9b21-4f2e-91b3-4a467353bcc0 (Secondary)
- nvd@nist.gov (Primary)
References for CVE-2022-30312
-
https://www.forescout.com/blog/
Blog - ForescoutThird Party Advisory
-
https://www.cisa.gov/uscert/ics/advisories/icsa-22-242-08
Honeywell Trend Controls Inter-Controller Protocol | CISAThird Party Advisory;US Government Resource