The Emerson DeltaV Distributed Control System (DCS) controllers and IO cards through 2022-04-29 misuse passwords. Access to privileged operations on the maintenance port TELNET interface (23/TCP) on M-series and SIS (CSLS/LSNB/LSNG) nodes is controlled by means of utility passwords. These passwords are generated using a deterministic, insecure algorithm using a single seed value composed of a day/hour/minute timestamp with less than 16 bits of entropy. The seed value is fed through a lookup table and a series of permutation operations resulting in three different four-character passwords corresponding to different privilege levels. An attacker can easily reconstruct these passwords and thus gain access to privileged maintenance operations. NOTE: this is different from CVE-2014-2350.
Published 2022-07-26 22:15:11
Updated 2023-01-24 16:06:41
Source MITRE
View at NVD,   CVE.org

Products affected by CVE-2022-29965

Exploit prediction scoring system (EPSS) score for CVE-2022-29965

0.04%
Probability of exploitation activity in the next 30 days EPSS Score History
~ 8 %
Percentile, the proportion of vulnerabilities that are scored at or less

CVSS scores for CVE-2022-29965

Base Score Base Severity CVSS Vector Exploitability Score Impact Score Score Source First Seen
5.5
MEDIUM CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:N/A:N
1.8
3.6
NIST

CWE ids for CVE-2022-29965

References for CVE-2022-29965

Jump to
This web site uses cookies for managing your session, storing preferences, website analytics and additional purposes described in our privacy policy.