Vulnerability Details : CVE-2022-23129
Plaintext Storage of a Password vulnerability in Mitsubishi Electric MC Works64 versions 4.04E (10.95.210.01) and prior and ICONICS GENESIS64 versions 10.90 to 10.97 allows a local authenticated attacker to gain authentication information and to access the database illegally. This is because when configuration information of GridWorX, a database linkage function of GENESIS64 and MC Works64, is exported to a CSV file, the authentication information is saved in plaintext, and an attacker who can access this CSV file can gain the authentication information.
Products affected by CVE-2022-23129
- cpe:2.3:a:iconics:genesis64:*:*:*:*:*:*:*:*
- cpe:2.3:a:mitsubishielectric:mc_works64:*:*:*:*:*:*:*:*
Exploit prediction scoring system (EPSS) score for CVE-2022-23129
0.07%
Probability of exploitation activity in the next 30 days
EPSS Score History
~ 19 %
Percentile, the proportion of vulnerabilities that are scored at or less
CVSS scores for CVE-2022-23129
Base Score | Base Severity | CVSS Vector | Exploitability Score | Impact Score | Score Source | First Seen |
---|---|---|---|---|---|---|
2.1
|
LOW | AV:L/AC:L/Au:N/C:P/I:N/A:N |
3.9
|
2.9
|
NIST | |
5.5
|
MEDIUM | CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:N/A:N |
1.8
|
3.6
|
NIST |
CWE ids for CVE-2022-23129
-
The product stores sensitive information in cleartext within a resource that might be accessible to another control sphere.Assigned by: nvd@nist.gov (Primary)
References for CVE-2022-23129
-
https://us-cert.cisa.gov/ics/advisories/icsa-22-020-01
ICONICS and Mitsubishi Electric HMI SCADA | CISAMitigation;Third Party Advisory;US Government Resource;VDB Entry
-
https://www.mitsubishielectric.com/en/psirt/vulnerability/pdf/2021-027_en.pdf
Mitigation;Vendor Advisory
-
https://jvn.jp/vu/JVNVU95403720/index.html
JVNVU#95403720: 三菱電機製GENESIS64およびMC Works64における複数の脆弱性Mitigation;Third Party Advisory;VDB Entry