The ABB HMI components implement hidden administrative accounts that are used during the provisioning phase of the HMI interface. These credentials allow the provisioning tool "Panel Builder 600" to flash a new interface and Tags (MODBUS coils) mapping to the HMI. These credentials are the idal123 password for the IdalMaster account, and the exor password for the exor account. These credentials are used over both HTTP(S) and FTP. There is no option to disable or change these undocumented credentials. An attacker can use these credentials to login to ABB HMI to read/write HMI configuration files and also to reset the device. This affects ABB CP635 HMI, CP600 HMIClient, Panel Builder 600, IDAL FTP server, IDAL HTTP server, and multiple other HMI components.
Published 2019-06-27 17:15:16
Updated 2023-05-16 11:15:01
Source MITRE
View at NVD,   CVE.org

Exploit prediction scoring system (EPSS) score for CVE-2019-7225

0.24%
Probability of exploitation activity in the next 30 days EPSS Score History
~ 62 %
Percentile, the proportion of vulnerabilities that are scored at or less

CVSS scores for CVE-2019-7225

Base Score Base Severity CVSS Vector Exploitability Score Impact Score Score Source First Seen
5.8
MEDIUM AV:A/AC:L/Au:N/C:P/I:P/A:P
6.5
6.4
NIST
8.8
HIGH CVSS:3.1/AV:A/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H
2.8
5.9
NIST

CWE ids for CVE-2019-7225

References for CVE-2019-7225

Products affected by CVE-2019-7225