A vulnerability has been identified in SIMATIC S7-300 CPU family (incl. related ET200 CPUs and SIPLUS variants) (All versions < V3.X.17), SIMATIC TDC CP51M1 (All versions < V1.1.8), SIMATIC TDC CPU555 (All versions < V1.1.1), SINUMERIK 840D sl (All versions < V4.8.6), SINUMERIK 840D sl (All versions < V4.94). Specially crafted packets sent to port 102/tcp (Profinet) could cause the affected device to go into defect mode. A restart is required in order to recover the system. Successful exploitation requires an attacker to have network access to port 102/tcp, with no authentication. No user interation is required. At the time of advisory publication no public exploitation of this security vulnerability was known.
Published 2020-03-10 20:15:19
Updated 2020-09-29 00:13:35
Source Siemens AG
View at NVD,   CVE.org

Products affected by CVE-2019-18336

Exploit prediction scoring system (EPSS) score for CVE-2019-18336

0.10%
Probability of exploitation activity in the next 30 days EPSS Score History
~ 41 %
Percentile, the proportion of vulnerabilities that are scored at or less

CVSS scores for CVE-2019-18336

Base Score Base Severity CVSS Vector Exploitability Score Impact Score Score Source First Seen
7.8
HIGH AV:N/AC:L/Au:N/C:N/I:N/A:C
10.0
6.9
NIST
7.5
HIGH CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H
3.9
3.6
NIST

CWE ids for CVE-2019-18336

  • The product does not properly control the allocation and maintenance of a limited resource, thereby enabling an actor to influence the amount of resources consumed, eventually leading to the exhaustion of available resources.
    Assigned by:
    • nvd@nist.gov (Primary)
    • productcert@siemens.com (Secondary)

References for CVE-2019-18336

Jump to
This web site uses cookies for managing your session, storing preferences, website analytics and additional purposes described in our privacy policy.
By using this web site you are agreeing to CVEdetails.com terms of use!