A vulnerability has been identified in DIGSI 4 (All versions < V4.92), EN100 Ethernet module DNP3 variant (All versions < V1.05.00), EN100 Ethernet module IEC 104 variant (All versions), EN100 Ethernet module IEC 61850 variant (All versions < V4.30), EN100 Ethernet module Modbus TCP variant (All versions), EN100 Ethernet module PROFINET IO variant (All versions). The device engineering mechanism allows an unauthenticated remote user to upload a modified device configuration overwriting access authorization passwords.
Published 2018-03-08 17:29:00
Updated 2021-07-13 12:15:09
Source Siemens AG
View at NVD,   CVE.org

Products affected by CVE-2018-4840

Exploit prediction scoring system (EPSS) score for CVE-2018-4840

0.14%
Probability of exploitation activity in the next 30 days EPSS Score History
~ 49 %
Percentile, the proportion of vulnerabilities that are scored at or less

CVSS scores for CVE-2018-4840

Base Score Base Severity CVSS Vector Exploitability Score Impact Score Score Source First Seen
5.0
MEDIUM AV:N/AC:L/Au:N/C:N/I:P/A:N
10.0
2.9
NIST
7.5
HIGH CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:H/A:N
3.9
3.6
NIST

CWE ids for CVE-2018-4840

  • The product does not perform any authentication for functionality that requires a provable user identity or consumes a significant amount of resources.