Eaton Power Xpert Meter 4000, 6000, and 8000 devices before 13.4.0.10 have a single SSH private key across different customers' installations and do not properly restrict access to this key, which makes it easier for remote attackers to perform SSH logins (to uid 0) via the PubkeyAuthentication option.
Published 2018-08-30 05:29:00
Updated 2020-08-24 17:37:01
Source MITRE
View at NVD,   CVE.org

Products affected by CVE-2018-16158

Exploit prediction scoring system (EPSS) score for CVE-2018-16158

3.30%
Probability of exploitation activity in the next 30 days EPSS Score History
~ 91 %
Percentile, the proportion of vulnerabilities that are scored at or less

Metasploit modules for CVE-2018-16158

  • Eaton Xpert Meter SSH Private Key Exposure Scanner
    Disclosure Date: 2018-07-18
    First seen: 2020-04-26
    auxiliary/scanner/ssh/eaton_xpert_backdoor
    Eaton Power Xpert Meters running firmware below version 12.x.x.x or below version 13.3.x.x ship with a public/private key pair that facilitate remote administrative access to the devices. Tested on: Firmware 12.1.9.1 and 13.3.2.10. Authors: - BrianWGray

CVSS scores for CVE-2018-16158

Base Score Base Severity CVSS Vector Exploitability Score Impact Score Score Source First Seen
10.0
HIGH AV:N/AC:L/Au:N/C:C/I:C/A:C
10.0
10.0
NIST
9.8
CRITICAL CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H
3.9
5.9
NIST

CWE ids for CVE-2018-16158

References for CVE-2018-16158