Controller DoS may occur due to buffer overflow when an error is generated in response to a specially crafted message. See Honeywell Security Notification for recommendations on upgrading and versioning.
Max CVSS
9.8
EPSS Score
0.05%
Published
2023-07-13
Updated
2024-04-22
Controller may be loaded with malicious firmware which could enable remote code execution. See Honeywell Security Notification for recommendations on upgrading and versioning.
Max CVSS
9.8
EPSS Score
0.24%
Published
2023-07-13
Updated
2024-04-22
Server or Console Station DoS due to heap overflow occurring during the handling of a specially crafted message for a specific configuration operation.  See Honeywell Security Notification for recommendations on upgrading and versioning.
Max CVSS
9.8
EPSS Score
0.05%
Published
2023-07-13
Updated
2024-04-22
Controller DoS due to stack overflow when decoding a message from the server.  See Honeywell Security Notification for recommendations on upgrading and versioning.
Max CVSS
9.8
EPSS Score
0.05%
Published
2023-07-13
Updated
2024-04-22
Experion server DoS due to heap overflow occurring during the handling of a specially crafted message for a specific configuration operation.  See Honeywell Security Notification for recommendations on upgrading and versioning.
Max CVSS
9.8
EPSS Score
0.05%
Published
2023-07-13
Updated
2024-04-22
Server receiving a malformed message can cause a pointer to be overwritten which can result in a remote code execution or failure. See Honeywell Security Notification for recommendations on upgrading and versioning.
Max CVSS
8.1
EPSS Score
0.04%
Published
2024-04-17
Updated
2024-04-17
Server hostname translation to IP address manipulation which could lead to an attacker performing remote code execution or causing a failure. See Honeywell Security Notification for recommendations on upgrading and versioning.
Max CVSS
8.1
EPSS Score
0.04%
Published
2024-04-17
Updated
2024-04-17
Server receiving a malformed message based on a using the specified key values can cause a stack overflow vulnerability which could lead to an attacker performing remote code execution or causing a failure. See Honeywell Security Notification for recommendations on upgrading and versioning.
Max CVSS
8.1
EPSS Score
0.04%
Published
2024-04-17
Updated
2024-04-17
Server receiving a malformed message based on a using the specified key values can cause a heap overflow vulnerability which could lead to an attacker performing remote code execution or causing a failure.  See Honeywell Security Notification for recommendations on upgrading and versioning.
Max CVSS
8.1
EPSS Score
0.04%
Published
2024-04-17
Updated
2024-04-17
Server receiving a malformed message to create a new connection could lead to an attacker performing remote code execution or causing a failure. See Honeywell Security Notification for recommendations on upgrading and versioning.
Max CVSS
8.1
EPSS Score
0.04%
Published
2024-04-17
Updated
2024-04-17
Server receiving a malformed message that uses the hostname in an internal table may cause a stack overflow resulting in possible remote code execution. See Honeywell Security Notification for recommendations on upgrading and versioning.
Max CVSS
8.1
EPSS Score
0.04%
Published
2024-04-17
Updated
2024-04-17
An attacker could potentially exploit this vulnerability, leading to the ability to modify files on Honeywell Experion ControlEdge VirtualUOC and ControlEdge UOC . This exploit could be used to write a file that may result in unexpected behavior based on configuration changes or updating of files that could result in subsequent execution of a malicious application if triggered. Honeywell recommends updating to the most recent version of the product. See Honeywell Security Notification for recommendations on upgrading and versioning. 
Max CVSS
9.1
EPSS Score
0.08%
Published
2024-01-30
Updated
2024-02-08
Session Fixation vulnerability in Honeywell PM43 on 32 bit, ARM (Printer web page modules) allows Session Credential Falsification through Prediction.This issue affects PM43 versions prior to P10.19.050004. Update to the latest available firmware version of the respective printers to version MR19.5 (e.g. P10.19.050006).
Max CVSS
8.8
EPSS Score
0.06%
Published
2023-09-12
Updated
2023-09-19

CVE-2023-3710

Public exploit
Improper Input Validation vulnerability in Honeywell PM43 on 32 bit, ARM (Printer web page modules) allows Command Injection.This issue affects PM43 versions prior to P10.19.050004. Update to the latest available firmware version of the respective printers to version MR19.5 (e.g. P10.19.050006).
Max CVSS
9.9
EPSS Score
70.42%
Published
2023-09-12
Updated
2023-09-19
** UNSUPPORTED WHEN ASSIGNED ** [An attacker can capture an authenticating hash and utilize it to create new sessions. The hash is also a poorly salted MD5 hash, which could result in a successful brute force password attack. Impacted product is BCM-WEB version 3.3.X. Recommended fix: Upgrade to a supported product such as Alerton ACM.] Out of an abundance of caution, this CVE ID is being assigned to better serve our customers and ensure all who are still running this product understand that the product is end of life and should be removed or upgraded. 
Max CVSS
9.8
EPSS Score
0.12%
Published
2023-06-28
Updated
2024-04-11
Saia Burgess Controls (SBC) PCD through 2022-05-06 allows Authentication bypass. According to FSCT-2022-0062, there is a Saia Burgess Controls (SBC) PCD S-Bus authentication bypass issue. The affected components are characterized as: S-Bus (5050/UDP) authentication. The potential impact is: Authentication bypass. The Saia Burgess Controls (SBC) PCD controllers utilize the S-Bus protocol (5050/UDP) for a variety of engineering purposes. It is possible to configure a password in order to restrict access to sensitive engineering functionality. Authentication functions on the basis of a MAC/IP whitelist with inactivity timeout to which an authenticated client's MAC/IP is stored. UDP traffic can be spoofed to bypass the whitelist-based access control. Since UDP is stateless, an attacker capable of passively observing traffic can spoof arbitrary messages using the MAC/IP of an authenticated client. This allows the attacker access to sensitive engineering functionality such as uploading/downloading control logic and manipulating controller configuration.
Max CVSS
8.1
EPSS Score
0.05%
Published
2022-07-28
Updated
2024-02-09
Honeywell ControlEdge through R151.1 uses Hard-coded Credentials. According to FSCT-2022-0056, there is a Honeywell ControlEdge hardcoded credentials issue. The affected components are characterized as: SSH. The potential impact is: Remote code execution, manipulate configuration, denial of service. The Honeywell ControlEdge PLC and RTU product line exposes an SSH service on port 22/TCP. Login as root to this service is permitted and credentials for the root user are hardcoded without automatically changing them upon first commissioning. The credentials for the SSH service are hardcoded in the firmware. The credentials grant an attacker access to a root shell on the PLC/RTU, allowing for remote code execution, configuration manipulation and denial of service.
Max CVSS
9.8
EPSS Score
0.34%
Published
2022-08-31
Updated
2022-09-07
Honeywell Experion LX through 2022-05-06 has Missing Authentication for a Critical Function. According to FSCT-2022-0055, there is a Honeywell Experion LX Control Data Access (CDA) EpicMo protocol with unauthenticated functionality issue. The affected components are characterized as: Honeywell Control Data Access (CDA) EpicMo (55565/TCP). The potential impact is: Firmware manipulation, Denial of service. The Honeywell Experion LX Distributed Control System (DCS) utilizes the Control Data Access (CDA) EpicMo protocol (55565/TCP) for device diagnostics and maintenance purposes. This protocol does not have any authentication features, allowing any attacker capable of communicating with the ports in question to invoke (a subset of) desired functionality. There is no authentication functionality on the protocol in question. An attacker capable of invoking the protocols' functionalities could issue firmware download commands potentially allowing for firmware manipulation and reboot devices causing denial of service.
Max CVSS
9.1
EPSS Score
0.07%
Published
2022-08-31
Updated
2024-02-13
Honeywell Experion PKS Safety Manager (SM and FSC) through 2022-05-06 has Insufficient Verification of Data Authenticity. According to FSCT-2022-0053, there is a Honeywell Experion PKS Safety Manager insufficient logic security controls issue. The affected components are characterized as: Honeywell FSC runtime (FSC-CPU, QPP), Honeywell Safety Builder. The potential impact is: Remote Code Execution, Denial of Service. The Honeywell Experion PKS Safety Manager family of safety controllers utilize the unauthenticated Safety Builder protocol (FSCT-2022-0051) for engineering purposes, including downloading projects and control logic to the controller. Control logic is downloaded to the controller on a block-by-block basis. The logic that is downloaded consists of FLD code compiled to native machine code for the CPU module (which applies to both the Safety Manager and FSC families). Since this logic does not seem to be cryptographically authenticated, it allows an attacker capable of triggering a logic download to execute arbitrary machine code on the controller's CPU module in the context of the runtime. While the researchers could not verify this in detail, the researchers believe that the microprocessor underpinning the FSC and Safety Manager CPU modules is incapable of offering memory protection or privilege separation capabilities which would give an attacker full control of the CPU module. There is no authentication on control logic downloaded to the controller. Memory protection and privilege separation capabilities for the runtime are possibly lacking. The researchers confirmed the issues in question on Safety Manager R145.1 and R152.2 but suspect the issue affects all FSC and SM controllers and associated Safety Builder versions regardless of software or firmware revision. An attacker who can communicate with a Safety Manager controller via the Safety Builder protocol can execute arbitrary code without restrictions on the CPU module, allowing for covert manipulation of control operations and implanting capabilities similar to the TRITON malware (MITRE ATT&CK software ID S1009). A mitigating factor with regards to some, but not all, of the above functionality is that these require the Safety Manager physical keyswitch to be in the right position.
Max CVSS
9.8
EPSS Score
0.66%
Published
2022-07-28
Updated
2022-08-05
Honeywell Alerton Ascent Control Module (ACM) through 2022-05-04 allows unauthenticated programming writes from remote users. This enables code to be store on the controller and then run without verification. A user with malicious intent can send a crafted packet to change and/or stop the program without the knowledge of other users, altering the controller's function. After the programming change, the program needs to be overwritten in order for the controller to restore its original operational function.
Max CVSS
8.0
EPSS Score
0.22%
Published
2022-07-15
Updated
2022-07-22
Honeywell Alerton Visual Logic through 2022-05-04 allows unauthenticated programming writes from remote users. This enables code to be stored on the controller and then run without verification. A user with malicious intent can send a crafted packet to change and/or stop the program without the knowledge of other users, altering the controller's function. After the programming change, the program needs to be overwritten in order for the controller to restore its original operational function.
Max CVSS
8.8
EPSS Score
0.20%
Published
2022-07-15
Updated
2022-07-22
If an attacker manages to trick a valid user into loading a malicious DLL, the attacker may be able to achieve code execution in Honeywell SoftMaster version 4.51 application’s context and permissions.
Max CVSS
8.8
EPSS Score
0.08%
Published
2022-09-16
Updated
2022-09-21
Matrikon, a subsidary of Honeywell Matrikon OPC Server (all versions) is vulnerable to a condition where a low privileged user allowed to connect to the OPC server to use the functions of the IPersisFile to execute operating system processes with system-level privileges.
Max CVSS
9.0
EPSS Score
0.10%
Published
2022-05-26
Updated
2022-06-08
Honeywell HDZP252DI 1.00.HW02.4 and HBW2PER1 1.000.HW01.3 devices allow a video replay attack after ARP cache poisoning has been achieved.
Max CVSS
9.8
EPSS Score
0.20%
Published
2022-02-24
Updated
2022-03-09
Honeywell Experion PKS C200, C200E, C300, and ACE controllers are vulnerable to unrestricted file uploads, which may allow an attacker to remotely execute arbitrary code and cause a denial-of-service condition.
Max CVSS
10.0
EPSS Score
0.26%
Published
2022-10-28
Updated
2022-11-02
50 vulnerabilities found