Stack-based buffer overflow in the Data Archiver service in GE Intelligent Platforms Proficy Historian before 3.5 SIM 17 and 4.x before 4.0 SIM 12 allows remote attackers to cause a denial of service (daemon crash) or possibly execute arbitrary code via crafted TCP message traffic.
Max CVSS
10.0
EPSS Score
23.36%
Published
2011-11-02
Updated
2013-05-21
Multiple stack-based buffer overflows in GE Intelligent Platforms Proficy Applications before 4.4.1 SIM 101 and 5.x before 5.0 SIM 43 allow remote attackers to cause a denial of service (daemon crash) or possibly execute arbitrary code via crafted TCP message traffic to (1) PRProficyMgr.exe in Proficy Server Manager, (2) PRGateway.exe in Proficy Server Gateway, (3) PRRDS.exe in Proficy Remote Data Service, or (4) PRLicenseMgr.exe in Proficy Server License Manager.
Max CVSS
10.0
EPSS Score
0.53%
Published
2011-11-02
Updated
2011-11-17
The Data Archiver service in GE Intelligent Platforms Proficy Historian 4.5 and earlier allows remote attackers to cause a denial of service (memory corruption) or possibly execute arbitrary code via a crafted session on TCP port 14000 to (1) ihDataArchiver.exe or (2) ihDataArchiver_x64.exe.
Max CVSS
10.0
EPSS Score
22.90%
Published
2012-03-15
Updated
2018-01-04
PRRDS.exe in the Proficy Remote Data Service in GE Intelligent Platforms Proficy Plant Applications 5.0 and earlier allows remote attackers to cause a denial of service (memory corruption) or possibly execute arbitrary code via a crafted TCP session on port 12299.
Max CVSS
10.0
EPSS Score
11.42%
Published
2012-03-15
Updated
2018-01-11
PRLicenseMgr.exe in the Proficy Server License Manager in GE Intelligent Platforms Proficy Plant Applications 5.0 and earlier allows remote attackers to cause a denial of service (memory corruption) or possibly execute arbitrary code via a crafted TCP session on port 12401.
Max CVSS
10.0
EPSS Score
11.42%
Published
2012-03-15
Updated
2018-01-11
rifsrvd.exe in the Remote Interface Service in GE Intelligent Platforms Proficy Real-Time Information Portal 2.6 through 3.5 SP1 allows remote attackers to cause a denial of service (memory corruption and service crash) or possibly execute arbitrary code via long input data, a different vulnerability than CVE-2012-3021 and CVE-2012-3026.
Max CVSS
10.0
EPSS Score
3.35%
Published
2012-11-01
Updated
2013-04-13
rifsrvd.exe in the Remote Interface Service in GE Intelligent Platforms Proficy Real-Time Information Portal 2.6 through 3.5 SP1 allows remote attackers to cause a denial of service (memory corruption and service crash) or possibly execute arbitrary code via long input data, a different vulnerability than CVE-2012-3010 and CVE-2012-3026.
Max CVSS
10.0
EPSS Score
3.35%
Published
2012-11-01
Updated
2013-04-13
rifsrvd.exe in the Remote Interface Service in GE Intelligent Platforms Proficy Real-Time Information Portal 2.6 through 3.5 SP1 allows remote attackers to cause a denial of service (memory corruption and service crash) or possibly execute arbitrary code via long input data, a different vulnerability than CVE-2012-3010 and CVE-2012-3021.
Max CVSS
10.0
EPSS Score
3.35%
Published
2012-11-01
Updated
2013-04-13
Absolute path traversal vulnerability in the download feature in FileDownloadServlet in GE Digital Energy MDS PulseNET and MDS PulseNET Enterprise before 3.1.5 allows remote attackers to read or delete arbitrary files via a full pathname.
Max CVSS
10.0
EPSS Score
61.43%
Published
2015-09-18
Updated
2015-09-23
General Electric (GE) Multilink ML800, ML1200, ML1600, and ML2400 switches with firmware before 5.5.0 and ML810, ML3000, and ML3100 switches with firmware before 5.5.0k have hardcoded credentials, which allows remote attackers to modify configuration settings via the web interface.
Max CVSS
10.0
EPSS Score
0.42%
Published
2016-06-09
Updated
2021-03-29
General Electric (GE) Bently Nevada 3500/22M USB with firmware before 5.0 and Bently Nevada 3500/22M Serial have open ports, which makes it easier for remote attackers to obtain privileged access via unspecified vectors.
Max CVSS
10.0
EPSS Score
0.85%
Published
2016-11-25
Updated
2016-11-28
GE Infinia/Infinia with Hawkeye 4 medical imaging systems all current versions are affected these devices use default or hard-coded credentials. Successful exploitation of this vulnerability may allow a remote attacker to bypass authentication and gain access to the affected devices.
Max CVSS
10.0
EPSS Score
0.23%
Published
2018-03-20
Updated
2019-10-09
An Improper Restriction of Operations within the Bounds of a Memory Buffer issue was discovered in GE D60 Line Distance Relay devices running firmware Version 7.11 and prior. The SSH functions of the device are vulnerable to buffer overflow conditions that may allow a remote attacker to execute arbitrary code on the device.
Max CVSS
10.0
EPSS Score
2.01%
Published
2018-02-19
Updated
2022-04-19
GE Fanuc Proficy Real-Time Information Portal 2.6 and earlier uses HTTP Basic Authentication, which transmits usernames and passwords in base64-encoded cleartext and allows remote attackers to steal the passwords and gain privileges.
Max CVSS
9.8
EPSS Score
1.14%
Published
2008-01-29
Updated
2024-02-14
A Weak Cryptography for Passwords issue was discovered in General Electric (GE) Multilin SR 750 Feeder Protection Relay, firmware versions prior to Version 7.47; SR 760 Feeder Protection Relay, firmware versions prior to Version 7.47; SR 469 Motor Protection Relay, firmware versions prior to Version 5.23; SR 489 Generator Protection Relay, firmware versions prior to Version 4.06; SR 745 Transformer Protection Relay, firmware versions prior to Version 5.23; SR 369 Motor Protection Relay, all firmware versions; Multilin Universal Relay, firmware Version 6.0 and prior versions; and Multilin URplus (D90, C90, B95), all versions. Ciphertext versions of user passwords were created with a non-random initialization vector leaving them susceptible to dictionary attacks. Ciphertext of user passwords can be obtained from the front LCD panel of affected products and through issued Modbus commands.
Max CVSS
9.8
EPSS Score
0.21%
Published
2017-06-30
Updated
2019-10-09
GE GEMNet License server (EchoServer) all current versions are affected these devices use default or hard-coded credentials. Successful exploitation of this vulnerability may allow a remote attacker to bypass authentication and gain access to the affected devices.
Max CVSS
9.8
EPSS Score
0.36%
Published
2018-03-20
Updated
2019-10-09
GE Xeleris versions 1.0,1.1,2.1,3.0,3.1, medical imaging systems, all current versions are affected, these devices use default or hard-coded credentials. Successful exploitation of this vulnerability may allow a remote attacker to bypass authentication and gain access to the affected devices.
Max CVSS
9.8
EPSS Score
0.36%
Published
2018-03-20
Updated
2019-10-09
GE Centricity PACS RA1000, diagnostic image analysis, all current versions are affected these devices use default or hard-coded credentials. Successful exploitation of this vulnerability may allow a remote attacker to bypass authentication and gain access to the affected devices.
Max CVSS
9.8
EPSS Score
0.23%
Published
2018-03-20
Updated
2019-10-09
A Stack-based Buffer Overflow issue was discovered in GE D60 Line Distance Relay devices running firmware Version 7.11 and prior. Multiple stack-based buffer overflow vulnerabilities have been identified, which may allow remote code execution.
Max CVSS
9.8
EPSS Score
1.11%
Published
2018-02-19
Updated
2020-09-18
Java remote method invocation (RMI) input port in GE MDS PulseNET and MDS PulseNET Enterprise version 3.2.1 and prior may be exploited to allow unauthenticated users to launch applications and support remote code execution through web services.
Max CVSS
9.8
EPSS Score
4.00%
Published
2018-06-04
Updated
2019-10-09
GE Communicator, all versions prior to 4.0.517, contains two backdoor accounts with hardcoded credentials, which may allow control over the database. This service is inaccessible to attackers if Windows default firewall settings are used by the end user.
Max CVSS
9.8
EPSS Score
0.21%
Published
2019-05-09
Updated
2022-11-30
GE Grid Solutions Reason RT Clocks, RT430, RT431, and RT434, all firmware versions prior to 08A05. The device’s vulnerability in the web application could allow multiple unauthenticated attacks that could cause serious impact. The vulnerability may allow an unauthenticated attacker to execute arbitrary commands and send a request to a specific URL that could cause the device to become unresponsive. The unauthenticated attacker may change the password of the 'configuration' user account, allowing the attacker to modify the configuration of the device via the web interface using the new password. This vulnerability may also allow an unauthenticated attacker to bypass the authentication required to configure the device and reboot the system.
Max CVSS
9.8
EPSS Score
0.24%
Published
2020-06-02
Updated
2020-06-08
A code injection vulnerability exists in one of the webpages in GE Reason RT430, RT431 & RT434 GNSS clocks in firmware versions prior to version 08A06 that could allow an authenticated remote attacker to execute arbitrary code on the system.
Max CVSS
9.8
EPSS Score
0.26%
Published
2022-03-18
Updated
2022-03-28
KEPServerEX: v6.0 to v6.9, ThingWorx Kepware Server: v6.8 and v6.9, ThingWorx Industrial Connectivity: All versions, OPC-Aggregator: All versions, Rockwell Automation KEPServer Enterprise, GE Digital Industrial Gateway Server: v7.68.804 and v7.66, Software Toolbox TOP Server: All 6.x versions are vulnerable to a stack-based buffer overflow. Opening a specifically crafted OPC UA message could allow an attacker to crash the server and remotely execute code.
Max CVSS
9.8
EPSS Score
0.54%
Published
2021-01-14
Updated
2021-01-21
GE UR IED firmware versions prior to version 8.1x with “Basic” security variant does not allow the disabling of the “Factory Mode,” which is used for servicing the IED by a “Factory” user.
Max CVSS
9.8
EPSS Score
0.21%
Published
2022-03-23
Updated
2022-04-01
128 vulnerabilities found